EMS NTI Enviromux E-16D
EMS NTI Enviromux E-1W
EMS NTI Enviromux E-2D
EMS NTI Enviromux E-5D
EMS NTI Enviromux E-MICRO
EMS NTI Enviromux E-MINI-LXO
NTI E-4WNSC-xx 4-Wire Non-Sensing Cable
Spesialis Elektronik – NTI E-4WNSC-xx 4-Wire Non-Sensing Cable
- For use in areas where E-LLDS-xx sensing cable is not required.
- Available lengths: 10/25/50/100 feet and custom lengths up to 1,000 feet.
- Contact an NTI product consultant for custom cable lengths
- M12 4-pin connectors.
- 22 AWG stranded bare copper conductors.
- Color-coded plenum-grade PVC insulation.
- Plenum-grade PVC jacket.
- Cable diameter: 0.136 in
- Operating temperature: 14 to 140°F (-10 to 60°C)
- Will ship in either white or gray.
- Regulatory approvals: CE, RoHS
- Compatible with E-ALDS Addressable Leak Detection Sensor and E-LLDC-xx Liquid Location Detection Sensor Cables.
NTI E-ALDS Addressable Leak Detection Sensor
Spesialis Elektronik – NTI E-ALDS Addressable Leak Detection Sensor
- Monitors up to 4,000 feet of E-LDDC-x Liquid Location Detection Sensor Cable.
- Detects the specific location of liquid presence.
- If multiple leaks are occurring at the same time, you will receive notification of the location for the leak closest to E-ALDS. Once that leak is cleared, you will receive notification of the next leak closest to the E-ALDS. This will continue until all leaks are cleared.
- Detects if there is a break in the cable.
- Detects the specific location of liquid presence.
- Supports up to 1,000 feet of E-4WNSC-x non-sensing cable.
- Leak location accuracy:
- 20 to 1,500 feet: ±(1ft + 0.5% of sensing cable length).
- 1,500 to 4,000 feet: ±1% of sensing cable length.
- Built-in Piezo buzzer emits loud beeps to alert personnel.
- Output level: 70dB at 1 foot
- Max current consumption: 13mA @ 5VDC, 18mA@12VDC
- Powered by E-2D/5D/16D.
- Compatible with E-2D/5D/16D.
- Interfaces with the E-2D/5D/16D via the RJ45 sensor port
- Extend up to 500 feet from the E-2D/5D/16D
- M12 4-pin connector for connecting E-LDDC-x Liquid Location Detection Sensor Cable or E-4WNSC-x Non-Sensing Cable
- Dimensions WxDxH: 3.21x2.5x1.22 in (82x64x31 mm)
- Operating temperature: 32 to 158°F (0 to 70°C).
- Regulatory approvals: CE, RoHS
- Integrated mounting brackets for easy surface/wall mounting.
- Use the included terminator at the end of the E-LDDC-x Liquid Location Detection Sensor Cable
NTI E-CDSx-y Legacy Chemical Detection Sensor
Spesialis Elektronik – NTI E-CDSx-y Legacy Chemical Detection Sensor
- For detecting the presence of chemical liquid.
- Reliably senses acids, bases, and other conductive liquids.
- Detects liquid depth >0.1" (2.5 mm).
- Minimum puddle: 0.6" (15 mm) diameter.
- Chemical resistant – cable functions normally after seven-day exposure to:
- Fresh deionized water
- Tap water
- Sulfuric acid, H2SO4 (98%)
- Sulfuric acid, H2SO4 (50%)
- Hydrochloric acid, HCl (37%)
- Sodium hydroxide, NaOH (10%)
- Aqua regia, HNO3+3 HCl
- Ethylene glycol, C2H6O2 (60% in DI water)
- Features a non-conductive polymer mesh that prevents false alarms caused by dirt/dust buildup, metal contact, or pressure on the rope.
- Voltage and current:
- Open Circuit: 5VDC max @ 1µA.
- Closed circuit: <300mV @ 10.7mA.
- RJ45 connector.
- Supports CAT5/5e/6 cable up to 1,000 ft. (305 m)
- Available chemical sensor cable (x) lengths: 1/10/50/100 feet.
- 100% waterproof
- Contact an NTI product consultant for cable lengths over 100 feet (30 meters) - supports up to 1,000 feet (305 meters).
- Available 2-wire plenum cable (y) lengths: 5/10/20/50/100 feet.
- Plenum rating: CL2P (UL)
- Diameter: 0.25 in (6.35mm)
- Contact an NTI product consultant for cable lengths over 100 feet (30 meters) – supports up to 1,000 feet (305 meters).
- Powered by E-SEMS-16U or SERIMUX-S-x.
- Requires the E-SEMS-16U or SERIMUX-S-x to operate.
- " Use self-adhesive clips (E-CLPxx-LD) to prevent sensor rope cable from shifting after installation.
NTI E-CDx-y Chemical Detection Sensor
Spesialis Elektronik – NTI E-CDx-y Chemical Detection Sensor
- For detecting the presence of chemical liquid.
- Reliably senses acids, bases, and other conductive liquids.
- Detects liquid depth >0.1" (2.5 mm).
- Minimum puddle: 0.6" (15 mm) diameter.
- Chemical resistant – cable functions normally after seven-day exposure to:
- Fresh deionized water
- Tap water
- Sulfuric acid, H2SO4 (98%)
- Sulfuric acid, H2SO4 (50%)
- Hydrochloric acid, HCl (37%)
- Sodium hydroxide, NaOH (10%)
- Aqua regia, HNO3+3 HCl
- Ethylene glycol, C2H6O2 (60% in DI water)
- Features a non-conductive polymer mesh that prevents false alarms caused by dirt/dust buildup, metal contact, or pressure on the rope.
- Voltage and current:
- Open Circuit: 5VDC max @ 1µA.
- Closed circuit: <300mV @ 10.7mA.
- Available chemical sensor cable (x) lengths: 1/10/50/100 feet.
- 100% waterproof
- Contact an NTI product consultant for cable lengths over 100 feet (30 meters) - supports up to 1,000 feet (305 meters).
- Available 2-wire plenum cable (y) lengths: 5/10/20/50/100 feet.
- Plenum rating: CL2P (UL)
- Diameter: 0.25 in (6.35mm)
- Contact an NTI product consultant for cable lengths over 100 feet (30 meters) – supports up to 1,000 feet (305 meters).
- Regulatory approvals: CE, RoHS
- Use self-adhesive clips (E-CLPxx-LD) to prevent sensor rope cable from shifting after installation.
NTI E-CLPxx-LD Self-Adhesive Clips for Liquid/Chemical Sensor Rope
Spesialis Elektronik – NTI E-CLPxx-LD Self-Adhesive Clips for Liquid/Chemical Sensor Rope
- Use to prevent sensor rope cable from shifting after installation
- Self-adhesive backing for easy installation
- Recommended distance between clips
- Cables less than 5 ft long: one clip at each end.
- Cables more than 5 ft long: minimum 5 ft apart.
- Material: Nylon
- Available quantities per package: 10, 100
- Compatible with E-LDSx-y, E-CDSx-y, E-LDx-y and E-CDx-y
NTI E-CMD Carbon Monoxide Detector, CO
- Continuous air monitoring.
- Pre-set alarm points alert at:
- 70 ppm after 60 to 240 minutes
- 150 ppm after 10 to 50 minutes
- 400 ppm after 4 to 15 minutes
- Flush or surface mount.
- Test functionality of electrochemical CO sensing cell.
- Connect to RJ45 or digital input sensor ports.
- Screw terminal
- To connect to the RJ45 inputs use CAT5/5e/6 cable terminated at one end with RJ45 connector. Connect the un-terminated end to the sensor screw terminal.
- Maximum cable length: 1000 ft (305m)
- LED indicators for operation status and system test.
- Current consumption: 40mA @ 12VDC.
- Powered by E-2D/5D/16D.
- Regulatory approvals: UL
NTI E-CO2-LC Carbon Dioxide Sensor, CO2
- Measures CO2 in a range of 0 to 5,000 ppm.
- Accuracy: ±(3% of reading + 50ppm) at 77°F (25°C)
- Sensing element: Single Beam Non-Dispersive Infrared (NDIR)
- 0 to 5 VDC output.
- Includes 12V/1A power supply.
- Current consumption: 60mA @ 12VDC.
- Weatherproof enclosure.
- IP65-rated water and dust protection.
- Operating temperature: 14 to 122°F (-10 to 50°C).
- Operating relative humidity: 0 to 80% non-condensing RH.
- Regulatory approvals: CE
- Requires the E-S5VDC sensor converter to operate with E-2D/5D/16D.
- E-S5VDC maximum cable length: 1000 ft (305 m).
- E-S5VDC powered by E-2D/5D/16D.
NTI E-DUST Optical Dust Sensor
- Detects the presence of dust and fine particles using an infrared emitting diode (IRED) and phototransistor.
- Able to distinguish smoke from house dust.
- RJ45 connector.
- Voltage supply: 5VDC
- Current consumption: < 50mA.
- Support CAT5/5e/6 cable to 1,000 ft (305 m).
- Dimensions (WxDxH) in: 5.9x2.3x1.2 (150x58x30 mm).
- Operating temperature: 32 to 149°F (0 to 65°C).
- Powered by E-2D/5D/16D.
- Compatible with E-2D/5D/16D.
- Regulatory compliance: RoHS.
NTI E-GD-MBP Gas Detector — Natural Gas, Methane, Butane, Propane, Hydrogen
- Use to detect leaks of combustible gas (natural gas, methane, propane, butane, hydrogen, acetylene, etc.)
- Choose between two levels of detection:
- First level:
- Methane: 10±3% LEL (0.44% vol. conc.)
- Propane: 18±3% LEL (0.30% vol. conc.)
- Iso-butane: 23±3% LEL (0.30% vol. conc.)
- Hydrogen: 9±3% LEL (0.36% vol. conc.)
- Second level:
- Methane: 18±3% LEL (0.80% vol. conc.)
- Propane: 30±3% LEL (0.50% vol. conc.)
- Iso-butane: 40±3 % LEL (0.50% vol. conc.)
- Hydrogen: 16±3% LEL (0.66% vol. conc.)
- First level:
- Continuous air monitoring.
- Audible alarm signal: 94 dB at 1 foot.
- Relay specifications: level selectable, normally open or normally closed, 250V AC, max 5A.
- Maximum cable length: 1000 ft (305m)
- Powered by E-2D/5D/16D.
- Current consumption: 150mA @ 12VDC.
- Regulatory approvals: CE
NTI E-H2S Hydrogen Sulfide Detector
- Use to monitor the presence of Hydrogen Sulfide from failed UPS (uninterrupted power supply) lead acid batteries, in paper mills, refineries, waste disposable facilities, etc.
- Measures H2S in a range of 0 to 50 ppm.
- 5A SPDT fan relay controls exhaust fans, valves, or louvers.
- Alerts are based solely on the measured H2S levels reported by the E-H2S.
- Mounts on a 4x4" electric box.
- Dimensions WxDxH (in): 4.5x4x2.13 (114x102x54 mm).
- Operating temperature: 0 to 125°F (-18 to 52°C).
- Operating and storage relative humidity: 10 to 90% non-condensing RH.
- Power consumption: 3W.
- Requires the E-S420MA-24V to operate.
- Maximum cable length: 500 ft (152 m).
- Powered by E-2D/5D/16D.
- Compatible with the E-2D/5D/16D.
- Regulatory approvals: ETL, UL.