As discussed in White Paper 64, Why Data Centers Must Prioritize Environmental Sustainability: Four Key Drivers, companies are seeking ways of decreasing their data center’s environmental footprint and of their company in general.
Spesialis Elektronik – UPS APC Easy UPS E3LUPS400KHS 400KVA
As discussed in White Paper 64, Why Data Centers Must Prioritize Environmental Sustainability: Four Key Drivers, companies are seeking ways of decreasing their data center’s environmental footprint and of their company in general. These needs apply to all data center sizes, from the largest multi-megawatt purpose-built data center to a single-rack micro data center in a branch office. Most vendors recognize these needs and therefore promote their product’s sustainability as a means to help their customers attain their sustainability goals.
As one of the leading companies in demonstrating sustainability1, Schneider Electric believes that customers care about three key topics when it
comes to sustainable products :
An environmental product declaration (EPD) summarizes the environmental life cycle data of a product or service and is normally valid for five years. These documents help specifiers make Uninterruptible Power Supply (UPS) decisions based on environmental impacts like carbon footprint and water use, making it easier to compare UPSs of the same category.
The International Organization for Standardization (ISO) publishes the standards that underly EPDs, in particular ISO 14025. EPDs must be based on life cycle assessment (LCA) data or life cycle inventory analysis (LCI) data, which are governed by the ISO 14040 standard. For more information on ISO standards, see Schneider Electric White Paper 70. Note that ISO 14040 is generic and applies to all types of products and services.
The following sections explain how to read an EPD, explain three key concepts of a 3-phase UPS PSR, and describe the typical carbon profile of a 3-phase UPS.
Reporting environmental data for a UPS
Program operators like the P.E.P. Association administer programs in compliance with ISO 14025 so that EPDs report the same type of information. They develop, approve, and publish product category rules (PCR) and product-specific rules (PSR) for Type III environmental declarations. All EPDs must be independently verified by internal2 or external experts and provide information need to track Scope 1, 2, and 33 emissions.
For this e-guide, the PCR related to a UPS covers electrical, electronic, and HVAC-R products and defines how vendors should perform the LCA. When the PCR isn’t detailed enough to develop EPDs for specific products, program operators develop PSRs.
What is a PEP and how to read it
PEP stands for Product Environmental Profile. The PEP Ecopassport association defines which mandatory information a PEP must provide. While the templates change from vendor to vendor, the key information needed for a UPS comparison is usually presented in the following order:
Product specific rules (PSR) for 3-phase UPS
The PSRs define rules for specific products within the larger product category. Due to their unique function, such as multiple operating modes, UPSs are one of those products that require their own product specific rules.
There are 3 key concepts in the UPS PSR that play a significant role in determining the life cycle carbon footprint of a UPS.
The RSL is the length of time the UPS is expected to remain in service. According to section 3.5.5.1 of the PSR, a 3-phase UPS over 10 kW has a service life of 15 years. This means that the life cycle assessment accounts for 15 years of UPS emissions. For example, if the electricity use emissions for the UPS is 100,000 kg CO2e per year, its lifetime electricity emissions would be 100,000 kg CO2e x 15 years or 1,500,000 kg CO2e
A load profile is meant to ensure that all manufacturers use the same assumptions to calculate electricity use. A load profile includes % load, length of time a UPS operates during its lifetime, and UPS operating mode.
For 3-phase UPSs greater than 10 kW, the electricity use is based on operating at:
Product specific rules (PSR) for 3-phase UPS (continued)
The percent load and operating mode are important because they determine the UPS’s efficiency at a specific load percentage. If a UPS has two operating modes, it will have two different efficiency values that characterize each mode. However, according to UPS PSR section 3.5.5.3, the electricity use calculation must be based on the UPS’s operating mode with the worst case weighted efficiency; which in most cases is double conversion.
The weighted efficiency for a 3-phase UPS (>10 kW) is calculated according to the formula:
Weighted efficiency = 25% x Eff25% + 50% x Eff50% + 25% x Eff75% + 0% x Eff100%
As more companies and consumers seek to reduce their environmental footprint, vendors are responding with claims of environmentally sustainable UPSs. Assessing the environmental sustainability of a UPS is complex and claims are difficult to ascertain without knowing the underlying assumptions and standards upon which they are made. By understanding the calculations behind the sustainability claims of the UPS you are considering, you can confidently choose a UPS that is better for your operations and the planet.
This e-guide defined and covered five life cycle stages that encompass a UPS’s environmental sustainability performance. We provided explanations for how to calculate the electricity-based UPS emissions. Finally, we offered guidance for how to accurately assess the sustainability of similar UPSs and a tool to help with UPS comparisons.
Terima kasih telah memesan UPS APC Easy UPS E3LUPS400KHS 400KVA, Kami Spesialis Elektronik sangat bersemangat untuk memproses pesananmu. Jangan lupa untuk memeriksa halaman toko kami untuk berbelanja lebih banyak lagi, ya!
produk |
Barang |
---|---|
merek | |
kondisi |
Baru |
jenis-ups |
On-line |
penempatan-ups |
Tower |
kapasitas-ups |
400KVA |
gelombang-inverter |
Pure Sine Wave |
Anda harus login untuk mengirimkan ulasan.
APC has become the industry-standard for reliable power and physical IT infrastructure. Our history of innovation has pushed our products into the global spotlight with infrastructure, management, and data security solutions protecting organizations around the world.